Housing and Installation
The electronics, including signal processor, LCD-display, analog and switch outputs, are fitted in a plastic housing with a degree of protection IP65. The housing can either be mounted directly on a 35 mm mounting rail or screwed to a wall. If the system replaces its predecessor ulm/es/b4, the mounting plate ps/nt:3.09174 can be used to screw the unit to the existing holes.
Connections
External cables are connected via PG-screw connections on the bottom of the housing. The wires are connected to screw terminals inside the housing. The terminals for 1.5 mm˛ are marked for easy installation.
Sensor Cable Connection
Twinax (according to IBM specification),
2 symmetrical leads, shielded
Length: <30 m
Also refer to transducer datasheet:
doc:D/ulm/s12me/001
System Settings
Refer to operating instructions:
doc:D/ps/ulm/esd/002
Features
|
Operating Voltage
|
24 V nom.
|
|
(18-30 Vdc or 15-24 Vac)
|
Current Consumption
|
approx. 150 mA
|
Measuring Range:
|
3 cm to 500 cm, greater distances on request
|
Measuring Rate
|
approx. 15 Hz
|
Outputs:
|
Current Output 4-20 mA (corresponding to 0-100 % distance)
|
|
5 Potential-free Relay-Switches (with 125 V, 1 A loading capacity),
|
|
incl. one error output
|
|
4 adjustable Switching Thresholds between 0 and 100 %
|
Serial Interfaces
|
RS232 and Current-Loop (without galvanic isolation)
|
Operator Control
|
LC-Display 2x8 Characters, 6 Keys
|
Dimensions:
|
252.5 x 68 x 136 mm (LxWxH)
|
|
Overall Height (with screw connections): 163 mm
|
Protection Class
|
IP65
| |
The separate application notes must be observed prior to operation!
Refer to doc:D/ulm/man/003
|
|
Picture: Functional Diagram
|
|
ps/ulm/2b
|
Pin-VG
|
Description
|
TX+
|
a2
|
Current Loop TX+, +12V
|
TX-
|
c2
|
Current Loop TX-
|
RX+
|
a4
|
Current Loop RX+
|
RX-
|
c4
|
Current Loop RX-, GND
|
UB1
|
c6
|
Power Supply
|
UB2
|
c8
|
Power Supply, GND
|
F1
|
a6
|
|
F2
|
a8
|
|
RX
|
a10
|
RS 232 RX
|
TX
|
a12
|
RS 232 TX
|
GNDx
|
c10
|
RS 232 GND, GND
|
Out+
|
a14
|
4-20mA Out+
|
Out-
|
a16
|
4-20mA GND
|
A5
|
c12
|
Switch Output 5
|
B5
|
c14
|
|
R5
|
c16
|
| |
|
ps/ulm/2b
|
Pin-VG
|
Description
|
A4
|
a18
|
Switch Output 4
|
B4
|
a20
|
|
R4
|
a22
|
|
A3
|
c18
|
Switch Output 3
|
B3
|
c20
|
|
R3
|
c22
|
|
A2
|
a24
|
Switch Output 2
|
B2
|
a26
|
|
R2
|
a28
|
|
A1
|
c24
|
Switch Output 1
|
B1
|
c26
|
|
R1
|
c28
|
|
Piezo 2
|
a30
|
PE
|
Piezo 4
|
c30
|
PE
|
Piezo 1
|
a32
|
Sensor Connection
|
Piezo 3
|
c32
|
| |
|
Order Number
|
Release
|
Description
|
ps/ulm/esd/a
|
1.0
|
Single-Channel ULM System
|
ulm/s12me
|
1.0
|
Ultrasonic Sensor
|
ps/nt:3.09174
|
1.4
|
Mounting Plate
| |
|
|
|
|
|
|
marco Systemanalyse und Entwicklung GmbH Hans-Böckler-Str. 2 . D-85221 Dachau Tel (+49) [0] 8131 5161 0 . Fax (+49) [0] 8131 5161 66 |
http://www.marco.de/E/D/ps/ulm/esd/001.html - Rev. 1.8 (2006-09-07)
All Rights Reserved Any questions or comments about this page? webmaster@marco.de |
|